A PPR pipe insulation heat loss calculation usually gets run after the damage: a code table that does not list your case, or an insulation quote at a thickness nobody can justify. A 100 m run of bare 32 mm PP-R at 60 °C in a 20 °C plant room loses about 33,700 kWh a year; under 20 mm of lagging, about 7,850 kWh.

The method is EN ISO 12241:2022: heat flow per metre equals the temperature difference divided by three resistances in series, the PP-R wall, the insulation and the air film on the outer surface. For a 32 x 5.4 mm PP-R hot line under 20 mm of 0.035 W/(m·K) lagging that gives 9.0 W/m, against 38.5 W/m bare. Every figure below is a still-air model result on published PP-R property data, not a field measurement and not a Hitze test.

Key Takeaways

  • q = Δθ ÷ (Rpipe + Rinsulation + Rsurface); each layer R = ln(De/Di) ÷ (2πλ); surface R = 1 ÷ (π·De·hse).
  • The #1 page for this query omits the surface film: its example claims 989 W/m; with the film it is 203 W/m.
  • 32 x 5.4 mm PP-R at 60 °C in 20 °C air: 38.5 W/m bare, 13.6 at 9 mm, 9.0 at 20 mm, 6.3 at 40 mm (λ 0.035).
  • The PP-R wall is worth 1.0 mm of lagging on a 32 mm pipe, 2.0 mm on a 63 mm pipe.
  • 63 x 10.5 mm at 6 °C in 25 °C / 80% RH air: 12 mm of elastomeric foam clears the 21.3 °C dew point; bright foil needs 28 mm.
  • The same chain is your GEG Anlage 8 Nummer 4 or ASHRAE 90.1 footnote e documentation.
From 4:58 this worked example draws the pipe, insulation and film resistances as one circuit, the chain Steps 2 and 3 use, and solves for thickness.
Calculate Pipe Insulation Thickness - Thermal Resistance Example Problem

What the Calculation Must Include, and What the Top Result Leaves Out

The page that currently ranks first for this query computes conduction through a bare 110 mm PP-R wall with Q = 2πkL(T1 − T2) ÷ ln(r2/r1), no surface film and no insulation. It reports 9,889.61 W for 10 m at a 60 K difference: 989 W per metre. Rerun the same pipe with the outer air film in the chain and it loses 203 W/m at a surface temperature of 64.5 °C. The wall-only formula overstates it 4.9 times.

The rulebook is EN ISO 12241:2022, the current edition; the 2008 text is withdrawn. Formula 6 gives each cylindrical layer a linear resistance of ln(De/Di) ÷ (2πλ), Formula 8 adds the layers, and Formula 18 closes the chain with the surface film, hsese − θa). Drop the film and the answer is wrong by a factor, not a percentage.

Step 1: Fix the Inputs

PP-R is sold by outside diameter and SDR, but the resistance depends on the wall. To DIN 8077 a PN 20 (SDR 6) pipe of 32 mm has a 5.4 mm wall and a 63 mm pipe has 10.5 mm. Published PP-R data sheets put the material’s conductivity at 0.23 W/(m·K) at 23 °C to DIN 52612-1; that is generic property data, not a Hitze measurement.

Take the insulation conductivity at the mean temperature of the layer, never the catalogue headline. Armacell’s AF/Armaflex sheet states the tube value as [33 + 0.1·θm + 0.0008·θm²] ÷ 1000 W/(m·K): 0.033 at 0 °C, 0.0383 at a 40 °C mean. ROCKWOOL’s RockLap H&V stone-wool sections list 0.033 at 10 °C, 0.037 at 50 °C and 0.044 at 100 °C. A 60 °C line under lagging runs a mean near 40 °C, so the 0 °C figure flatters the result by about 15%.

Two inputs set the surface film: the finish and the room. Plastic, paint and elastomeric skins radiate at an emissivity near 0.9, bright aluminium foil near 0.05. A hot line needs the air temperature; a chilled line also needs the relative humidity, because its design condition is a surface that never drops below the dew point.

Four cut lengths of yellow PPR-CU pipe in rising outside diameters, end-on, showing the polypropylene wall thickness around the copper-lined bore
The wall is the input the SDR hides: on these four PPR-CU sizes the polypropylene wall grows with the outside diameter, and it is the ratio of outer to inner diameter, not the wall in millimetres, that sets Rpipe in Step 2. Library photo of Hitze PPR-CU; the calculation uses plain PP-R walls to DIN 8077.

Step 2: Add the Resistances and Find the Surface Coefficient

For the 32 x 5.4 mm hot line under 20 mm of 0.035 lagging the chain reads: wall ln(32/21.2) ÷ (2π × 0.23) = 0.285 m·K/W; lagging ln(72/32) ÷ (2π × 0.035) = 3.688; surface 1 ÷ (π × 0.072 × 8.95) = 0.494. Total 4.467 m·K/W, so q = 40 K ÷ 4.467 = 9.0 W/m. The lagging carries 83% of the resistance, the air film 11%, the wall 6%.

The surface coefficient hse is the part people guess. ISO 12241 builds it from a radiative part plus a convective part. Radiation is ε × 5.67 × 10-8 × 4Tav³, about 5.3 W/(m²·K) at ε 0.9 and 0.3 at ε 0.05 near room temperature. Convection on a small horizontal pipe in still air follows the laminar form 1.32 × (Δθ/De)0.25, about 3.7 W/(m²·K) for a 72 mm surface running 4.4 K warm. Together, roughly 9 W/(m²·K) for a non-metallic finish and roughly 4 for bright foil.

The standard’s shortcut, hse = CA + 0.05·Δθ with CA = 8.5 for non-metallic surfaces, gives 8.7 W/(m²·K) here, within 4%, though it is stated for pipes of 0.25 to 1.0 m outer diameter. Since Δθ depends on the surface temperature you are solving for, iterate twice; hse of 8 or 10 instead of 8.95 only shifts the 20 mm result from 8.84 to 9.06 W/m.

Step 3: Hot Case, 32 mm PP-R at 60 °C

Run the chain at each thickness and the curve flattens fast. Bare, the 32 x 5.4 mm pipe loses 38.5 W/m with its skin at 49.0 °C. The first 9 mm of 0.035 lagging cuts that to 13.6 W/m; 20 mm reaches 9.0 W/m; the step from 20 to 40 mm buys only 2.7 W/m more. Over 100 m that is 33,700 kWh a year bare, 11,900 at 9 mm and 7,850 at 20 mm.

Hot case: 32 x 5.4 mm PP-R, water 60 °C, still air 20 °C. ISO 12241 series-resistance model, computed 12 September 2026; still-air model results, not field measurements.
Insulation thickness (mm)λ 0.035 code basis (W/m)Elastomeric, ε 0.9 (W/m)Foil-faced stone wool, ε 0.05 (W/m)Surface temp, λ 0.035 (°C)
0 (bare)38.538.5n/a49.0
913.614.712.028.5
1311.212.210.326.4
209.09.78.524.4
258.08.77.623.6
307.37.97.023.0
406.36.96.222.2
Heat loss of a 32 x 5.4 mm PP-R line at 60 °C by insulation thickness, three insulants01020304050091320253040Heat loss (W/m)Insulation thickness (mm)λ 0.035 code basisElastomeric, ε 0.9Foil-faced stone wool, ε 0.05
The first 9 mm removes almost two thirds of the loss; 20 mm reaches 9.0 W/m and the step from 20 to 40 mm buys only 2.7 W/m more, with the three insulants inside 1 W/m of each other beyond 20 mm. Method: EN ISO 12241 series-resistance model (PP-R wall, insulation layer, outer air film with iterated surface coefficient), PP-R lambda 0.23 W/(m·K), DIN 8077 SDR 6 wall 5.4 mm, water 60 °C, still air 20 °C; insulation at lambda 0.035 (code basis), AF/Armaflex elastomeric at its mean-temperature lambda with emissivity 0.9, and foil-faced stone wool at 0.037 with emissivity 0.05; computed 12 September 2026, still-air model results, not measurements.

Two things in that table matter for a PP-R specification. The material columns sit within 1 W/m of the code column from 20 mm up: elastomeric runs hotter inside and slightly worse, foil-faced wool gains from its low emissivity. And the PP-R wall’s 0.285 m·K/W equals 1.0 mm of 0.035 lagging on this pipe, 2.0 mm on a 63 x 10.5 mm pipe. German and US rules both let you count it; it replaces a millimetre or two, not a layer.

Step 4: Chilled Case, 63 mm PP-R at 6 °C, Surface Above the Dew Point

On a chilled line the number that matters is the outer surface temperature: below the dew point it sweats, drips onto ceilings and soaks mineral wool until it insulates like a sponge. At 25 °C and 80% RH the dew point is 21.3 °C; ISO 12241 Table 3 puts it the other way round, a surface at most 3.7 K below the air at 24 to 26 °C and 80% RH.

Run the 63 x 10.5 mm pipe at 6 °C through the same chain and watch the surface. Bare, it sits at 12.8 °C and streams. Under 9 mm of elastomeric foam it reaches 20.5 °C, still 0.8 K short; 13 mm lifts it to 21.6 °C and the line stays dry. The minimum is 12 mm, at a heat gain of 8.7 W/m.

Chilled case: 63 x 10.5 mm PP-R, water 6 °C, still air 25 °C at 80% RH, dew point 21.3 °C. ISO 12241 model, computed 12 September 2026; the surface must stay at or above 21.3 °C.
Insulation thickness (mm)Elastomeric, ε 0.9: surface (°C)Foil-faced wool, ε 0.05: surface (°C)Verdict at 80% RH
0 (bare)12.810.4Condenses on both
920.517.7Condenses on both
1321.619.0Elastomeric dry; foil condenses
1922.520.2Elastomeric dry; foil condenses
2523.021.0Elastomeric dry; foil 0.3 K short
3223.421.7Both dry
Outer surface temperature of a 63 x 10.5 mm chilled PP-R line at 6 °C by insulation thickness, two finishes, against the 21.3 °C dew point05101520250913192532Outer surface temperature (°C)Insulation thickness (mm)Elastomeric, ε 0.9Foil-faced wool, ε 0.05Dew point 21.3 °C
The bright foil finish sits closer to the water temperature at every thickness, so it clears the 21.3 °C dew point only at about 28 mm where elastomeric foam with a high-emissivity skin clears it at 12 to 13 mm. Method: EN ISO 12241 series-resistance model with iterated surface coefficient, PP-R lambda 0.23 W/(m·K), DIN 8077 SDR 6 wall 10.5 mm, water 6 °C, still air 25 °C; elastomeric foam at its mean-temperature lambda with emissivity 0.9, foil-faced stone wool at 0.034 with emissivity 0.05; dew point 21.3 °C from the Magnus formula at 25 °C and 80% RH; computed 12 September 2026, still-air model results, not measurements.

Installers are usually surprised by the foil column. A bright finish that saves about 9% on a hot pipe works against you on a cold one. A low-emissivity skin exchanges less heat with the room, so it sits closer to the water temperature and needs 28 mm of stone wool to clear the dew point where 12 mm of foam will do. BS 5422:2023’s condensation tables, in ROCKWOOL’s selection, run the same way: 20 mm on a high-emissivity surface against 40 mm on a low-emissivity one for a pipe up to 60.3 mm at 5 °C.

Treat the chilled result as a floor: ISO 12241’s own introduction warns that dew formation cannot be reliably assured from basic calculations because local humidity varies, and 85% RH cuts the allowed difference to 2.6 K. Size for the worst week.

Step 5: Code Equivalence and Elastomeric vs Mineral Wool

The model earns its keep when the code table does not fit your material. GEG Anlage 8 states every thickness for a 0.035 W/(m·K) product; Nummer 3 says to convert for anything else by recognised calculation methods. Hold the lagging resistance constant, ln(72/32) ÷ 0.035 = 23.17, and the 20 mm band on the 32 mm pipe becomes 22.9 mm of elastomeric at its 40 °C conductivity of 0.0383, or 21.7 mm of foil-faced stone wool at 0.037. Nummer 4 lets you claim equivalence while counting the pipe wall, the 1.0 mm from Step 3.

ASHRAE 90.1 does the same job in inches. Table 6.8.3-1 of Addendum aq to the 2019 edition requires 1.0 in (25.4 mm) on a pipe under 1½ in at 105 to 140 °F, assuming 0.22 to 0.28 Btu·in/(h·ft²·°F) at a 100 °F mean, which is 0.0317 to 0.0404 W/(m·K). Elastomeric at that mean is 0.263 and stone wool about 0.248 in those units, both inside the range, so the table value stands and lands at 7.9 W/m on the hot curve. Outside the range, footnote a gives T = r{(1 + t/r)K/k − 1}.

Footnote e is the PP-R clause: a non-metallic pipe with more thermal resistance than steel may carry less insulation if you document that pipe plus lagging transfers no more heat per foot than steel with the table thickness. The chain above is that documentation; edition and adoption vary by state, so confirm which 90.1 the authority having jurisdiction enforces.

Two short plastic pipe samples on a workbench, one sleeved in black closed-cell elastomeric foam and one in a foil-faced mineral wool section, cut ends showing the insulation thickness (illustration)
The two finishes the tables above disagree about: a matt black elastomeric skin radiates at an emissivity near 0.9, a bright foil facing near 0.05, which is why the foil section needs more than twice the thickness on a chilled line. Illustration, not a Hitze product photo.
Elastomeric foam vs foil-faced stone wool on PP-R. Sources: Armacell AF/Armaflex TDS and ROCKWOOL RockLap H&V datasheet, read 12 September 2026; thickness row from this article’s model.
PropertyElastomeric foam (AF/Armaflex)Stone-wool section (RockLap H&V)Verdict for PP-R
Conductivity λ (W/m·K)0.033 at 0 °C; 0.0383 at 40 °C mean0.033 at 10 °C; 0.037 at 50 °C; 0.044 at 100 °CEqual at chilled means; wool edges ahead hot
Vapour resistanceClosed cell, μ ≥ 10,000; no separate barrierFibrous; relies on foil facing and taped jointsElastomeric on chilled lines
Service temperature (°C)−50 to +1100 to 250; foil face limited to 80Either covers PP-R’s hot-water duty
Finish emissivityAbout 0.9 (black skin)About 0.05 (bright foil)Foil cuts hot loss about 9%; hurts chilled
Dew-point thickness, 63 mm at 6 °C (mm)1228Elastomeric, by a wide margin

The verdict follows the two cases. Chilled and cold-water PP-R gets closed-cell elastomeric: its own vapour resistance does the barrier’s job, and 12 mm clears the dew point where the foil-faced section needs 28 mm. Heating and hot-water PP-R can take either; foil-faced stone wool loses about 9% less at the same thickness, elastomeric fits faster around fused sockets and bends.

Run the equivalence on the real wall figure
For MEP contractors, specifiers and distributors filing a Nummer 4 or footnote e equivalence: Hitze PP-R, OD 20 to 110 mm, four constructions, DIN 8077/8078 and EN ISO 15874, no MOQ on general ordering. Ask for the per-size wall and SDR table first.

See the PP-R range and wall tables

What to Ask the Pipe Supplier, and What We Check

Every input on the pipe side of the chain is a supplier data point. Ask for the per-size wall and SDR from the current technical data sheet, not a catalogue OD list, because the 1 to 2 mm the wall is worth under Nummer 4 or footnote e depends on it. Ask which construction the run uses, too: fibre-reinforced and aluminium-composite pipes carry different walls, as the construction comparison sets out.

What Hitze checks before a pipe leaves the plant

Hitze’s PP-R is made to DIN 8077/8078 and EN ISO 15874, with SKZ testing on pipe and fittings and a DVGW type examination on the drinking-water line. Its in-house checks measure OD, wall at multiple points and ovality against the S-series tables on every size from OD 20 to 110 mm before hydrostatic testing, which is the dimensional record an equivalence file needs. The project piping supply page covers how sizes and constructions are matched to a tender, the SDR and PN ratings guide explains the wall classes, and the insulation decision guide settles which code duty applies first.

Extruded black plastic pipe leaving the crosshead die and passing through the sizing ring on a Hitze extrusion line
The wall is fixed here, at the die and sizing ring, before any QC gauge sees it; the per-size OD, wall and ovality record taken downstream is the pipe-side input an equivalence file under GEG Nummer 4 or ASHRAE footnote e has to cite. Hitze extrusion line, library photo.

Conclusion

Do it in this order. One: fix the six inputs, with the insulation conductivity at its mean temperature and the finish emissivity chosen honestly. Two: build the three-resistance chain and iterate the surface temperature twice. Three: on a hot line, stop where the next 10 mm buys under 1 W/m. Four: on a chilled line, size to the dew point at the worst humidity anyone will commit to; bright foil needs more, not less. Five: file the chain as your Nummer 4 or footnote e documentation, counting the pipe wall at 1 to 2 mm. The answer flips only outdoors or in moving air, where still-air coefficients no longer apply.

Before you sign the thickness, pull the wall table for the exact SDR you are installing and rerun Step 2 with it.

Frequently Asked Questions

How do I calculate the heat loss through pipe insulation on a PPR pipe?

Divide the water-to-air temperature difference by the sum of three resistances per metre: the PP-R wall ln(Do/Di)/(2πλ), the insulation ln(De/Do)/(2πλ), and the surface film 1/(π·De·hse), per EN ISO 12241:2022. For 32 x 5.4 mm PP-R at 60 °C under 20 mm of 0.035 lagging that gives 9.0 W/m.

Does the PPR pipe wall count as insulation?

It counts, but for very little: at 0.23 W/(m·K) the wall of a 32 x 5.4 mm pipe equals 1.0 mm of 0.035 lagging, and a 63 x 10.5 mm wall equals 2.0 mm. GEG Anlage 8 Nummer 4 and ASHRAE 90.1 footnote e both let you include it in an equivalence calculation.

What surface heat transfer coefficient should I use for an indoor pipe?

About 9 W/(m²·K) for a plastic, painted or elastomeric finish and about 4 W/(m²·K) for bright foil in still air, from radiation plus laminar convection. ISO 12241’s shortcut hse = CA + 0.05·Δθ, with CA = 8.5 for non-metallic surfaces, lands within 4% of that for the hot case here.

Why does foil-faced insulation need to be thicker on a chilled PPR line?

A low-emissivity foil exchanges less heat with the room, so its surface sits closer to the cold water and drops below the dew point sooner. On a 63 mm PP-R line at 6 °C in 25 °C, 80% RH air, 12 mm of elastomeric foam clears 21.3 °C but foil-faced stone wool needs 28 mm.

Which insulation conductivity value goes into the calculation?

The value at the mean temperature of the layer, which is what GEG Anlage 8 also prescribes: 40 °C for heating lines and 10 °C for cold lines. AF/Armaflex declares 0.033 W/(m·K) at 0 °C but 0.0383 at 40 °C; RockLap H&V is 0.033 at 10 °C and 0.037 at 50 °C.

Written by Justin, Technical & export team, Hitze Group.

Reviewed 12 September 2026. Profile